Wiring Requirements for the Drive

4-5

4.2

Control and Signal Wire Sizes

The terminal block on the SP 600 I/O interface board provides
terminals for 24 V or 115 VAC power for the control inputs,
depending on the I/O card installed in the drive. Refer to 4.3 for
signal and control wiring specifications.

4.3

Recommended Motor Lead Lengths

Important:

To reduce line disturbances and noise, motor lead
length should not exceed 300 feet for any non-
Reliance Electric motor or any non-inverter duty
motor.

The length of cable between the drive and motor may be limited for
various applications reasons. The primary reasons are:

Reflected wave

Cable charging

!

ATTENTION: Verify the voltage rating of the I/O interface
board before wiring any user devices. Failure to observe this
precaution could result in damage to, or destruction of, the
equipment.

Table 4.3 – Recommended Signal and Control Wire

Signal

Type

Wire Type(s)

Description

Minimum

Insulation

Rating

Analog I/O

Belden 8760/
9460 (or equiv.)

18AWG, twisted pair,
100% shield with drain

1

.

300V, 60

°

C

(140

°

F)

Belden 8770
(or equiv.)

18AWG,
3-conductor, shielded for
remote pot only.

Unshielded
Control

Per US NEC or
applicable local
code

300V, 60

°

C

(140

°

F)

Shielded
Control

Multi-conductor
cable such as
Belden 8770
(or equiv.)

18 AWG, 3-conductor
shielded.

300V, 60

°

C

(140

°

F)

1

If the wires are short and contained within a cabinet which has no sensitive circuits,
the use of shielded wire may not be necessary, but is always recommended.