Parameter Descriptions

3-83

Selects the type of input signal being used for analog input 1 and 2. These inputs can
be configured as 10VDC (unipolar or bipolar) or as 4-20mA inputs. See scaling
parameters Analog ln 1 (322 and 323) and Analog ln 2 (325 and 326).

Enables/disables the square root function for each analog input.

320

Anlg In Config

Range:

See figure 3.31

Default:

See figure 3.31

Access:

0

Path: Inputs & Outputs>Analog Inputs

See also:

322, 323, 325, 326

Figure 3.31 – Anlg ln Config (320)

1

x

x

1

x

x

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Current
0 =Voltage
x =Reserved

Bit #

Factory Default Bit Values

Analog In1

Analog In2

Analog ln 1

Bit

Term

0 to 10 VDC or

-10 to +10 VDC

Bit 0 = 0

1, 2 (17 to 18 not jumpered)

4 to 20 mA

Bit 0 = 1

1, 2 (17 to 18 jumpered)

Analog ln 2

Bit

Term

-0 to 10 VDC or
-10 to +10 VDC

Bit 1 = 0

3, 4 (19 to 20 not jumpered)

4 to 20 mA

Bit 1 = 1

3, 4 (19 to 20 jumpered)

321

Anlg In Sqr Root

Range:

See figure 3.32

Default:

See figure 3.32

Access:

2

Path: Inputs & Outputs>Analog Inputs

See also:

Figure 3.32 – Anlg in Sqr Root (321)

1

x

x

1

x

x

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Current
0 =Voltage
x =Reserved