320 anlg in config, 321 anlg in sqr root – Rockwell Automation Liqui-Flo DBT Reach Drive User Manual
Page 109

Parameter Descriptions
3-83
Selects the type of input signal being used for analog input 1 and 2. These inputs can
be configured as 10VDC (unipolar or bipolar) or as 4-20mA inputs. See scaling
parameters Analog ln 1 (322 and 323) and Analog ln 2 (325 and 326).
Enables/disables the square root function for each analog input.
320
Anlg In Config
Range:
See figure 3.31
Default:
See figure 3.31
Access:
0
Path: Inputs & Outputs>Analog Inputs
See also:
322, 323, 325, 326
Figure 3.31 – Anlg ln Config (320)
1
x
x
1
x
x
x
x
x
x
x
x
x
x
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1 =Current
0 =Voltage
x =Reserved
Bit #
Factory Default Bit Values
Analog In1
Analog In2
Analog ln 1
Bit
Term
0 to 10 VDC or
-10 to +10 VDC
Bit 0 = 0
1, 2 (17 to 18 not jumpered)
4 to 20 mA
Bit 0 = 1
1, 2 (17 to 18 jumpered)
Analog ln 2
Bit
Term
-0 to 10 VDC or
-10 to +10 VDC
Bit 1 = 0
3, 4 (19 to 20 not jumpered)
4 to 20 mA
Bit 1 = 1
3, 4 (19 to 20 jumpered)
321
Anlg In Sqr Root
Range:
See figure 3.32
Default:
See figure 3.32
Access:
2
Path: Inputs & Outputs>Analog Inputs
See also:
Figure 3.32 – Anlg in Sqr Root (321)
1
x
x
1
x
x
x
x
x
x
x
x
x
x
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1 =Current
0 =Voltage
x =Reserved
Bit #
Factory Default Bit Values
Analog Out1
Analog Out2