2.5.4 The I/O Control Board

Figure 2.2 shows the I/O control board and terminal block locations. The control board
provides a mounting point for the various Reach Drive I/O options. To remove the
cassette, loosen the two screw latches as shown in Figure 2.7. (A).

2.5.5 I/O Terminal Blocks

!

ATTENTION: You must stay within the minimum and maximum wire size
range. Failure to observe this precaution can result in severe equipment
damage, bodily injury, or loss of life.

Table 2.7 – I/O Terminal Block Specifications

No.

Name

Description

Wire Size Range4

Torque

Maximum Minimum Maximum

Recommended

1

I/O
Terminal
Block

Signal &
control
connections

2.1 mm

2

(14 AWG)

0.30

mm

2

(22
AWG)

0.6 N-m
(5.2 lb.-in.)

0.6 N-m
(5.2 lb.-in.)

2

Encoder
Terminal
Block

Encoder
power &
signal
connections

0.75 mm

2

(18 AWG)

0.196

mm

2

(24
AWG)

0.6 N-m
(5.2 lb.-in.)

0.6 N-m
(5.2 lb.-in.)

Figure 2.7 – Reach Drive Typical Control Board and I/O Terminal Blocks

PIN 1

PIN 1

1

2

A

JUMPER

4. Maximum/minimum sizes that the terminal block will accept - these are not recommendations.