379 dig out setpt – Rockwell Automation Liqui-Flo DBT Reach Drive User Manual
Page 125
Advertising
![background image](/manuals/581003/125/background.png)
Parameter Descriptions
3-99
Sets the digital output value from a communication device.
Example: Set Data ln B1 (302) to 379. The first three bits of this value will determine
the setting of Digital Outx Sel (380, 384, 388), which should be set to 30 = Param Cntl.
379
Dig Out Setpt
Range:
See figure 3.35
Default:
See figure 3.35
Access:
2
Path: Inputs & Outputs>Digital Outputs
See also: 380
Figure 3.35 – Dig Out Setpt
0
0
x
0
x
x
x
x
x
x
x
x
x
x
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1 =Output Energized
0 =Output De-energized
x =Reserved
Bit #
Digital Out1
Digital Out2
Digital Out3