Parameter Descriptions

3-85

Selects drive response when an analog signal loss is detected. Signal loss is defined
as an analog signal less than 1 V or 2 mA. The signal loss event ends and normal
operation resumes when the input signal level meets or exceeds 1.5 V or 3 mA.

One of the selections (1=Fault) stops the drive on signal loss. All other choices make it
possible for the input signal to return to a usable level while the drive is still running.

Analog In 2 Hi sets the highest input value to the analog input 2 scaling block.

Anlg ln Config (320) defines if the input value will be -/+10V or 0-20 mA.

Sets the lowest input value to the analog input 2 scaling block.

Anlg ln Config (320) defines if the input value will be -/+10V or 0-20 mA.

If set below 4 mA, Analog ln x Loss (324) should be “Disabled.”

324

Analog In 1 Loss

Range:

0 = Disabled
1 = Fault
2 = Hold Input (use last frequency command)
3 = Set Input Lo (use Minimum Speed as frequency command)
4 = Set Input Hi (use Maximum Speed as frequency command)
5 = Go to Preset1 (use Preset 1 as frequency command)
6 = Hold OutFreq (maintain last output frequency)

Default:

0 = Disabled

Access:

2

Path: Inputs & Outputs>Analog Inputs

See also:

91, 92, 190

!

ATTENTION: Setting parameter 324 to a value greater than 1 allows the
input signal to return to a usable level while the drive is running. If a lost
analog signal is restored while the drive is running, the drive will ramp to
the restored reference level at the rate specified in Accel Time 1 (140),
Accel Time 2 (141), Decel Time 1 (142), and Decel Time 2 (143). Be
aware that an abrupt speed change may occur depending upon the new
reference level and the rate specified in these parameters. Failure to
observe this precaution could result in bodily injury.

325

Analog In 2 Hi

Range:

4.000 to 20.000 mA [0.001 mA]
-/+10.000 V [0.001 V]; 0.0 to 10.000 V [0.001 V]

Default:

10.000 V

Access:

2

Path: Inputs & Outputs>Analog Inputs

See also:

91, 92

326

Analog In 2 Lo

Range:

4.000 to 20.000 mA [0.001 mA]
-/+10.000 V [0.001 V]; 0.0 to 10.000 V [0.001 V]

Default:

0.000 V

Access:

2

Path: Inputs & Outputs>Analog Inputs

See also:

91, 92