Appendix D-12

DBT Reach Drive User Manual

Skip Frequency

Some machinery may have a resonant operating frequency that must be avoided to
minimize the risk of equipment damage. To assure that the motor cannot continuously
operate at one or more of the points, skip frequencies are used. Skip Frequencies
(084-086) are available to set the frequencies to be avoided.

The value programmed into the skip frequency parameters sets the center point for an
entire “skip band” of frequencies. The width of the band (range of frequency around
the center point) is determined by Skip Freq Band (87). The range is split, half above
and half below the skip frequency parameter.

If the commanded frequency of the drive is greater than or equal to the skip (center)
frequency and less than or equal to the high value of the band (skip plus 1/2 band),
the drive will set the output frequency to the high value of the band. See (A) in D.14.

If the commanded frequency is less than the skip (center) frequency and greater than
or equal to the low value of the band (skip minus 1/2 band), the drive will set the output
frequency to the low value of the band. See (B) in D.14.

Figure D.15 – Skip Frequency

Frequency

Time

(A)

(A)

(B)

(B)

Skip Frequency

Command

Frequency

Drive Output
Frequency

Skip + 1/2 Band

Skip – 1/2 Band

35 Hz

30 Hz

25 Hz