91 speed ref a hi, 92 speed ref a lo – Rockwell Automation Liqui-Flo DBT Reach Drive User Manual

Page 48

Advertising
background image

3-22

DBT Reach Drive User Manual

Selects the source of the speed reference to the drive unless Preset Speed 1-7
(101-107)

or Speed Ref B (93) is selected.

Note that the manual reference command and input HIM Control can override the
reference control source.

Scales the upper value of the Speed Ref A Sel (90) selection when the source is an
analog input.

Scales the lower value of the Speed Ref A Sel (90) selection when the source is an
analog input.

!

ATTENTION: Removing and replacing the LCD HIM while the drive is
running may cause an abrupt speed change if the LCD HIM is the
selected reference source. The drive will ramp to the reference level
provided by the HIM at the rate specified in Accel Time 1 (140), Accel
Time 2 (141), Decel Time 1 (142) and Decel Time 2 (143). Be aware that
an abrupt speed change may occur depending upon the new reference
level and the rate specified in these parameters. Failure to observe this
precaution could result in bodily injury.

91

Speed Ref A Hi

Range:

-/+Maximum Speed [0.1 Hz or 0.1 RPM]

Default:

Maximum Speed

Access:

1

Path: Speed Command>Speed References

See also:

79, 82, 190

92

Speed Ref A Lo

Range:

-/+Maximum Speed [0.1 Hz or 0.01 RPM]

Default:

0.0

Access:

1

Path: Speed Command>Speed References

See also: 79, 81, 190