Parameter Descriptions

3-87

Selects whether the signed value or absolute value of a parameter is used before
being scaled to drive the analog output.

341

Anlg Out Absolut

Range:

See figure 3.34

Default:

See figure 3.34

Access:

2

Path: Inputs & Outputs>Analog Outputs

See also:

Figure 3.34 – Anlg Out Absolute (341)

1

x

x

1

x

x

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Absolute
0 =Signed
x =Reserved

Bit #

Factory Default Bit Values

Analog Out1

Analog Out2

342
345

Analog Out1Sel
Analog Out2 Sel

Range:

0 = Output Freq
1 = Command Freq
2 = Output Amps
3 = Torque Amps
4 = Flux Amps
5 = Output Power
6 = Output Volts
7 = DC Bus Volts
8 = PI Reference
9 = PI Feedback
10 = PI Error
11 = PI Output
12 = %Motor OL
13 = %Drive OL
14 = CommandedTrq
15 = MtrTqrCurRef
16 = Speed Ref
17 = Speed Fdbk
18 = Pulse ln Ref
19 = Torque Est
20 = Scale Block 1
21 = Scale Block 2
22 = Scale Block 3
23 = Scale Block 4
24 = Param Cntl
25 = SpdFb NoFilt

Default:

0 = Output Freq

Access:

1

Path: Inputs & Outputs>Analog Outputs

See also:

1 - 7, 12, 135 - 138, 219, 220