669 adj volt trimsel, 670 adj volt trim hi, 671 adj volt trim lo – Rockwell Automation Liqui-Flo DBT Reach Drive User Manual
Page 153: 672 adj volt trim

Parameter Descriptions
3-127
Selects the source of the voltage trim that is added to or subtracted from the voltage
reference.
Scales the upper value of the Adj Volt TrimSel (669) selection when the source is an
analog input.
Scales the lower value of the Adj Volt TrimSel (669) selection when the source is an
analog input.
669
Adj Volt TrimSel
Range:
0 = Reserved
1 = Analog In 1
2 = Analog In 2
3-6 = Reserved
7-8 = Not Used
9 = MOP Level
10 = Reserved
11-17 = Preset Volt 1-7
18-22 = DPI Port 1-5
24 = Output Power
25 = Out Current
Default:
2 = Analog In 2
Access:
2
Path: Applications>Adjust Voltage
See also:
670
Adj Volt Trim Hi
Range:
0.0 to 100.0% of Drive Rated Volts [0.1%]
Default:
100.0%
Access:
2
Path: Applications>Adjust Voltage
See also:
671
Adj Volt Trim Lo
Range:
0.0 to 100.0% of Drive Rated Volts [0.1%]
Default:
0.0%
Access:
2
Path: Applications>Adjust Voltage
See also:
672
Adj Volt Trim %
Range:
-/+100.0% of Drive Rated Volts [0.1%]
Default:
0.0%
Access:
2
Path: Applications>Adjust Voltage
See also: