62 ir voltage drop, 63 flux current ref, 64 ixo voltage drop – Rockwell Automation Liqui-Flo DBT Reach Drive User Manual

Page 40: 66 autotune torque

Advertising
background image

3-14

DBT Reach Drive User Manual

Value of volts dropped across the resistance of the motor stator. Used only when
Motor Cntl Sel (53) is set to Sensrls Vect, SV Economize or FVC Vector.

Value of amps for full motor flux. Used only when Motor Cntl Sel (53) is set to Sensrls
Vect, SV Economize or FVC Vector.

Sets the value of the voltage drop across the leakage inductance of the motor at rated
motor current. Used only when Motor Cntl Sel (53) is set to Sensrls Vect, SV
Economize or FVC Vector.

Specifies motor torque applied to the motor during the flux current and inertia tests
performed during an autotune.

62

IR Voltage Drop

Range:

0.0 to Motor NP Volts x 0.25 [0.1 VAC]

Default:

Based on Drive Rating

Access:

1

Path: Motor Control>Torq Attributes

See also:

53, 61

63

Flux Current Ref

Range:

0.00 to Motor NP FLA [0.01 Amps]

Default:

Based on Drive Rating

Access:

1

Path: Motor Control>Torq Attributes

See also:

53, 61

64

Ixo Voltage Drop

Range:

0.00 to 230.0, 460.0 or 575.0 VAC [0.1 VAC]

Default:

Based on Drive Rating

Access:

1

Path: Motor Control>Torq Attributes

See also:

66

Autotune Torque

Range:

0.0 to 150% [0.1%]

Default:

50%

Access:

1

Path: Motor Control>Torq Attributes

See also:

53