604 brk release time, 605 zerospdfloattime, 606 float tolerance – Rockwell Automation Liqui-Flo DBT Reach Drive User Manual

Page 144: 607 brk set time

Advertising
background image

3-118

DBT Reach Drive User Manual

Sets the amount of time between commanding the brake to release and the start of
drive acceleration. In Encoderless mode, this parameter sets the time to release the
brake after the drive starts.

Sets the amount of time the drive is below Float Tolerance (606) before the brake is
set. Not used in Encoderless Torque Prove mode.

Sets the frequency level where the float timer starts. Also sets the frequency level
where the brake will be closed in Encoderless Torque Prove mode.

Defines the amount of delay time between commanding the brake to be set and the
start of brake proving.

604

Brk Release Time

Range:

0.00 to 10.00 sec [0.01 sec]

Default:

0.10 sec

Access:

2

Path: Applications>Torque Proving

See also:

605

ZeroSpdFloatTime

Range:

0.1 to 500.0 sec [0.1 sec]

Default:

5.0 sec

Access:

2

Path: Applications>Torque Proving

See also:

606

Float Tolerance

Range:

0.1 to 5.0 Hz or 3.0 to 150.0 RPM [0.1 Hz or 0.1RPM]

Default:

0.2 Hz or 6.0 RPM

Access:

2

Path: Applications>Torque Proving

See also:

607

Brk Set Time

Range:

0.00 to 10.00 sec [0.01 sec]

Default:

0.10 sec

Access:

2

Path: Applications>Torque Proving

See also: