Troubleshooting

4-5

Motor
Type Cflct

21

Motor Type (90) has been set to Sync PM or Sync Reluc, and one or
more of the following exist:

Torque Perf Mode = “Sensrls Vect,” “SV Economizer” or “Fan/Pmp
V/Hz.”

Flux Up Time is greater than 0.0 secs.

Speed Mode is set to “Slip Comp.”

Autotune = “Static Tune” or “Rotate Tune.”

NP Hz
Conflict

22

Fan/pump mode is selected in Torq Perf Mode (53), and the ratio of
Motor NP Hertz (43) to Maximum Freq (55) is greater than 26.

Power
Loss

3

Drive has sensed a power line loss.

Precharge

Active

1

Drive is in the initial DC bus precharge state.

Prof Step
Cflct

50

An error is detected in trend step(s).

Set if Sleep mode is enabled

Set if:

any profile step uses “Encoder Incr” and/or “Enc Absolute” and
Motor Cntl Sel (53) is not set to “FVC Vector” and Feedback
Select (80) is not set to “Encoder” or “Simulator” and
Speed/Torque Mod (88) = “7” (Pos/Spd Prof).

a Step Type is configured for “Dig Input” and the Step Value is
greater than 6, less than -6, or zero or the digital input selected
with Digital lnx Sel is not set to “57” (Prof Input).

Cleared if none of the above occur.

PTC
Conflict

31

PTC is enabled for Analog ln 1, which is configured as a 0-20 mA
current source in Anlg ln Config (320).

Sleep
Config

29

Sleep/Wake configuration error. With Sleep-Wake Mode (178) =
Direct, possible causes include: drive is stopped and Wake Level <
Sleep Level. “Stop=CF”, “Run,” “Run Forward” and “Run Reverse” is
not configured in Digital lnx Sel.

Speed
Ref Cflct

27

Speed Ref x Sel or PI Reference Sel is set to “Reserved.”

Start At
Powerup

4

Start At Powerup (168) is enabled. Drive may start at any time
within 10 seconds of drive powerup.

Table 4.2 – Alarm Descriptions (Continued)

Alarm

No

.

Ty

p

e

Description