Defines the amount of time at or above Wake Level before a start command is issued.

Defines the analog input level that will stop the drive.

Defines the amount of time at or below Sleep Level before a stop command is issued.

Sets the reaction to a loss of input power. Power loss is recognized when:

DC bus voltage is

≤ 73% of DC Bus Memory and Power Loss Mode is set to Coast. DC

bus voltage is

≤ 82% of DC Bus Memory and Power Loss Mode is set to Decel.

181

Wake Time

Range:

0.0 to 1000.0 Secs [0.1 sec]

Default:

0.0 sec

Access:

1

Path: Dynamic Control>Restart Modes

See also:

180

182

Sleep Level

Range:

4.000 mA, 0.000 V / Wake Level [0.001 mA, 0.001 V]

Default:

5.000 mA, 5.000 V

Access:

1

Path: Dynamic Control>Restart Modes

See also:

183

183

Sleep Time

Range:

0.0 to 1000.0 secs [0.1 sec]

Default:

0.0 sec

Access:

1

Path: Dynamic Control>Restart Modes

See also:

182

184

Power Loss Mode

Range:

0 = Coast
1 = Decel
2 = Continue
3 = Coast input
4 = Decel input

Default:

0 = Coast

Access:

1

Path: Dynamic Control>Power Loss

See also:

13, 184