Rockwell Automation Liqui-Flo DBT Reach Drive User Manual

Page 200

Advertising
background image

A-4

DBT Reach Drive User Manual

Table A.6 – Liquid Coolant

Coolant Type

50% / 50%
Water/Propolyne Glycol

Maximum Particle Size in
Coolant

5 microns

Minimum Flow Rate

2 gpm

Nominal Flow Rate

2.5 gpm

Maximum Flow Rate

6 gpm

Pressure Drop

<5 psi at 2.5 gpm, 20

° C

Maximum Coolant
Temperature

60

° C

Maximum Inlet Pressure

50 psi

Table A.7 – Output Specifications

Output Voltage

0 to 460 V RMS at nominal 480 V RMS input. Output will be
460 V RMS

Output Frequency
Range

0 to 420 Hz

Switching Frequency

4 kHz Base. 2, 4, 8, 10 KHz selectable with derating.
Derating at 8 and 10 KHz.

Continuous Output
Power

100 KW (150 HP)

Continuous Output
Current

180 Amps RMS

Peak Output Current (3
sec maximum)

270 Amps RMS (3 sec / 60 sec)

Peak Output Current
(60 sec)

198 Amps RMS (1 min / 10 min)

Efficiency at Maximum
Power, Nominal
Voltage

>97.5%

Power Loss at Full
Load

1900 W at 100 KW

Power Loss to Air

200 W at 110 KW