B.2 logic status word – Rockwell Automation Liqui-Flo DBT Reach Drive User Manual

Page 205

Advertising
background image

Logic Command/Status Words

B-3

B.2 Logic Status Word

Logic Bits

Command

Description

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

X Ready

0 = Not Ready
1 = Ready

X

Active

0 = Not Active
1 = Active

X

Command
Direction

0 = Reverse
1 = Forward

X

Actual
Direction

0 = Reverse
1 = Forward

X

Accel

0 = Not Accelerating
1 = Accelerating

X

Decel

0 = Not Decelerating
1 = Decelerating

X

Alarm

0 = No Alarm
1 = Alarm

X

Fault

0 = No Fault
1 = Fault

X

At Speed

0 = Not at Reference
1 = At Reference

X X X

Local
Control

000 = Port 0 (TB)
001 = Port 1
010 = Port 2
011 = Port 3
100 = Port 4
101 = Port 5
110 = Reserved
111 = No Local

X X X X

Reference
Source

0000 = Ref A Auto
0001 = Ref B Auto
0010 = Preset 2 Auto
0011 = Preset 3 Auto
0100 = Preset 4 Auto
0101 = Preset 5 Auto
0110 = Preset 6 Auto
0111 = Preset 7 Auto
1000 = Term Blk Manual
1001 = DPI 1 Manual
1010 = DPI 2 Manual
1011 = DPI 3 Manual
1100 = DPI 4 Manual
1101 = DPI 5 Manual
1110 = Reserved
1111 = Jog Ref

Advertising