Rockwell Automation Liqui-Flo DBT Reach Drive User Manual

Page 114

Advertising
background image

3-88

DBT Reach Drive User Manual

Selects the source of the value that drives the analog output.

Table 3.3 – Analog Out1/2 Sel

Options

Analog Out1/2 Lo Value

Analog Out1/2 Hi

P.341 = Signed

P.341 = Absolute

0 = Output Freq

-Maximum Speed 0 Hz

+ Maximum Speed

1 = Command Spd

-Maximum Speed 0 Hz/RPM

+ Maximum Speed

2 = Output Amps

0 Amps

0 Amps

200% Rated

3 = Torque Amps

-200% Rated

0 Amps

200% Rated

4 = Flux Amps

0 Amps

0 Amps

200% Rated

5 = Output Power

0 kW

0 kW

200% Rated

6 = Output Volts

0 Volts

0 Volts

120% Rated Input Volts

7 = DC Bus Volts

0 Volts

0 Volts

200% Rated Input Volts

8 = PI Reference

-100%

0%

100%

9 = PI Feedback

-100%

0%

100%

10 = PI Error

-100%

0%

100%

11 = PI Output

-100%

0%

100%

12 = %Motor OL

0%

0%

100%

13 = %Drive OL

0%

0%

100%

14 = CommandedTrq

-800% Rated

0%

800% Rated

15 = MtrTrqCurRef

-200% Rated

0%

200% Rated

16 = Speed Ref

-Maximum Speed 0 Hz/RPM

+ Maximum Speed

17 = Speed Fdbk

-Maximum Speed 0 Hz/RPM

+ Maximum Speed

18 = Pulse ln Ref

-25200.0 RPM

0 Hz/RPM

+ Maximum Speed

19 = Torque Est

-800%

0%

800%

20 = Scale Block 1

0%

0%

100%

21 = Scale Block 2

0%

0%

100%

22 = Scale Block 3

0%

0%

100%

23 = Scale Block 4

0%

0%

100%

24 = Param Cntl

0%

0%

100%

25 = SpdFb NoFilt

0%

0%

100%