179 sleep-wake ref, 180 wake level – Rockwell Automation Liqui-Flo DBT Reach Drive User Manual

Page 74

Advertising
background image

3-48

DBT Reach Drive User Manual

Selects the source of the input controlling the Sleep-Wake function.

Defines the analog input level that will start the drive.

!

ATTENTION: Enabling the Sleep-Wake function can cause unexpected
machine operation during the Wake mode. Failure to observe these
precautions can result in damage to the equipment and/or personal injury.

Table 3.2 – Conditions Required to Start Drive when Sleep-Wake is Enabled

1

2

3

Configured

Digital

Input(s)

After

Power-Up

After Fault

After Stop

Stop-CF Cmd

(HIM or

TermBlk)

Clear Faults Cmd

(TB or V*S Utilities)

HIM, TB, or Network Stop

Stop

Stop
Closed
Wake
Signal

Stop Closed
Wake Signal

Start/Run Cmd

4

Stop Closed

Stop Closed

Direct Mode: Analog Sig>Sleep Level

5

Invert Mode: Analog Sig<Sleep Level

5

Start/Run Cmd

Enable

Enable
Closed
Wake
Signal

Enable Closed
Wake Signal

Start/Run Cmd

4

Enable Closed
Wake Signal

Enable Closed

Direct Mode: Analog Sig>Sleep Level

5

Invert Mode: Analog Sig<Sleep Level

5

Start/Run Cmd

Run
Run For.
Run Rev.

Run
Closed
Wake
Signal

Run Cmd

4

Wake Signal

Run Closed
Wake Signal

Run Cmd

4

Wake Signal

1

When power is cycled, restart will occur if all conditions above are met.

2

When Sleep-Wake Mode is enabled, drive start will occur if all conditions above are met.

3

The Sleep-Wake function and Speed Reference may be assigned to the same analog input.

4

Start/Run Cmd must be cycled.

5

Signal does not have to be greater than Wake level.

179

Sleep-Wake Ref

Range:

1 = Analog In 1
2 = Analog In 2

Default:

2 = Analog In 2

Access:

1

Path: Dynamic Control>Restart Modes

See also:

180

Wake Level

Range:

Sleep Level / 20.000 mA, 10.000 volts [0.001 mA, 0.001 V]

Default:

6.000 mA, 6.000 V

Access:

1

Path: Dynamic Control>Restart Modes

See also:

181