1 i/o terminal designations -8, 1 i/o terminal designations – Rockwell Automation Liqui-Flo DBT Reach Drive User Manual
Page 14

2-8
DBT Reach Drive User Manual
2.5.1 I/O Terminal Designations
Table 2.2 – I/O Terminal Designations
No.
Signal
Factory
Default
Description
Rel.
Param.
1
Analog In 1 (-)
1
2
Isolated
3
, bipolar, differential
+/- 10V/4-20mA, 11 bit and
sign, 88k ohm input
impedance. For 4-20mA, a
jumper must be installed at
terminals 17 and 18 (or 19
and 20).
320-
327
2
Analog In 1 (+)
1
3
Analog In 2 (-)
1
4
Analog In 2 (+)
1
5
Port Common
-
For (+) and (-) 10V port
references.
6
Analog Out 1 (-)
2
Bipolar (current output is not
bipolar), +/- 10V/4-20mA, 11
bit and sign, voltage mode -
limit current to 5 mA. Current
mode - maxz load resistance
is 400 ohms.
340-
347
7
Analog Out 1 (+)
8
Analog Out 2 (-)
9
Analog Out 2 (+)
10
HW PTC Input 1
-
1.8k ohm PTC, Internal 3.32k
ohm pull-up resistor
238
259
11
Digital Out 1 - N.C.
4
Fault
Max. Resistive Load:
240V AC/30V DC -- 1200VA,
150W
Max. Current: 5A, Min. Load
10mA
Max. Inductive Load:
240V AC/30V DC - 840VA,
105W
Max. Current: 3.5A, Min.
Load: 10mA
380-
391
12
Digital Out 1 Common
13
Digital Out 1 - N.O.
4
NOT
Fault
14
Digital Out 2 - N.C.
4
NOT
Run
15
Digital Out 2/3 Com
16
Digital Out 3 - N.O.
4
Run
1
16
32