Parameter Descriptions

3-101

Selects the drive status that will energize an output relay.

Sets the relay activation level for options 10-15 in Digital Out”x” Sel. Units are
assumed to match the above selection (i.e., At Freq = Hz, At Torque = Amps).

Sets the on delay time for the digital outputs. This is the time between the occurrence
of a condition and activation of the relay.

54 = Prof @ Step 13
55 = Prof @ Step 14
56 = Prof @ Step 15
57 = Prof @ Step 16
58 = TB in Manual

Default:

380: 1 = Fault
384: 4 = Run
388: 4 = Run

Access:

1

Path: Inputs & Outputs>Digital Outputs

See also:

1-4, 12, 48, 53, 137, 147, 157, 184, 218, 381-383, 385, 386, 390

380
384
388

Digital Out1 Sel
Digital Out2 Sel
Digital Out3 Sel

381
385
389

Digital Out1 Level
Digital Out2 Level
Digital Out3 Level

Range:

0.0 to 819.2 [0.1]

Default:

0.0

Access:

1

Path: Inputs & Outputs>Digital Outputs

See also: 380

382
386
390

Digital Out1 OnTime
Digital Out2 OnTime
Digital Out3 OnTime

Range:

0.00 to 600.00 sec [0.1 sec]

Default:

0.00 sec

Access:

2

Path: Inputs & Outputs>Digital Outputs

See also:

380