4-12

DBT Reach Drive User Manual

NVS I/O
Checksum

109

EEprom checksum error.

1.

Cycle power and repeat
function.

2.

Replace Main Control
Board.

NVS I/O
Failure

110

EEprom I/O error.

1.

Cycle power and repeat
function.

2.

Replace Main Control
Board.

Output Phase
Loss

21

Current in one or more phases
has been lost or remains
below a preset level.

Check the drive and motor
wiring. Check for
phase-to-phase continuity at
the motor terminals. Check for
disconnected motor leads.

OverSpeed
Limit

25

Functions such as slip
compensation or bus
regulation have attempted to
add an output frequency
adjustment greater than that
programmed in Overspeed
Limit (83).

Remove excessive load or
overhauling conditions or
increase Overspeed Limit (83).

OverVoltage

5

DC bus voltage exceeded
maximum value.

Monitor the AC line for high line
voltage or transient conditions.
Bus overvoltage can also be
caused by motor regeneration.
Extend the decel time or install
dynamic brake option.

Parameter
Chksum

100

The checksum read from the
board does not match the
checksum calculated.

1.

Restore defaults.

2.

Reload user set if used.

Params
Defaulted

48

The drive was commanded to
write default values to
EEPROM.

1.

Clear the fault or cycle
power to the drive.

2.

Program the drive
parameters as needed.

Phase U to
Grnd

38

A phase-to-ground fault has
been detected between the
drive and motor in this phase.

1.

Check the wiring between
the drive and motor.

2.

Check motor for grounded
phase.

3.

Replace drive.

Phase V to
Grnd

39

Phase W to
Grnd

40

Phase UV
Short

41

Excessive current has been
detected between these two
output terminals.

1.

Check the motor and drive
output terminal wiring for a
shorted condition.

2.

Replace drive.

Phase VW
Short

42

Phase UW
Short

43

Table 4.5 – Fault Descriptions and Corrective Actions (Continued)