3-52

DBT Reach Drive User Manual

Allows configuration of the operation of all attached HIM devices (independent of
Logic Source Sel (89)). Upper word (bits 16-31) are reserved.

At Power Down:

Inactive = Preload HIM reference with zero at power-up.
Active = Save HIM references at power down and preload them at power-up.

Manual Mode:

Inactive = Transition from Auto to Manual causes only reference to be controlled from
the requesting HIM.

Active = Transition from Auto to Manual causes reference and control (Start, Jog,
Direction, Clear Faults) to be controlled from the requesting HIM.

HIM Disable:

Inactive: HIM Start, Jog, Direction, and Clear Fault commands are functional.
Active: HIM Start, Jog, Direction, and Clear Fault commands are disabled.

Enables/disables a feature to automatically load the present auto frequency reference
value into the HIM when Manual is selected. Allows smooth speed transition from Auto
to Manual.

192

Save HIM Ref

Range:

See figure 3.8

Default:

See figure 3.8

Access:

2

Path: Utility>HIM Ref Config

See also:

Figure 3.8 – Save HIM Ref (192)

0

x

0

1

x

x

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

Bit #

Factory Default Bit Values

At P

owr Do

wn

Man

ual Mode

OIM Disab

le

Reser

ved

193

Man Ref Preload

Range:

0 = Disabled
1 = Enabled

Default:

1 = Enabled

Access:

2

Path: Utility>HIM Ref Config

See also: