Application Notes

Appendix D-7

Process PI for Standard Control

The internal PI function of the Reach Drive provides closed loop process control with
proportional and integral control action. The function is designed for use in
applications that require simple control of a process without external control devices.
The PI function allows the microprocessor of the drive to follow a single process
control loop.

The PI function reads a process variable input to the drive and compares it to a
desired setpoint stored in the drive. The algorithm will then adjust the output of the PI
regulator, changing drive output frequency to try and make the process variable equal
the setpoint.

It can operate as trim mode by summing the PI loop output with a master speed
reference.

Or, it can operate as control mode by supplying the entire speed reference. This
method is identified as “exclusive mode.”

Figure D.8 – Trim Mode

Figure D.9 – Control Mode

+

Spd Cmd

Process PI

Controller

Linear Ramp

& S-Curve

+

+

+

PI Enabled

Speed Control

Spd Ref

PI Ref

PI Fbk

Slip Adder

Open

Loop

Slip

Comp

Process

PI

Spd Cmd

Process PI

Controller

Linear Ramp

& S-Curve

+

+

PI Enabled

Speed Control

Spd Ref

PI Ref

PI Fbk

Slip Adder

Open

Loop

Slip

Comp

Process

PI