Parameter Descriptions
3-107
Sets the scale factor/gain for the Pulse Input when Encoder Z Chan (423) is set to
Pulse Input. Calculate for desired speed command as follows:
For Hz, [Pulse ln Scale] = Input Pulse Rate (Hz)/Desired Cmd. (Hz)
For RPM, [Pulse ln Scale] = (Input Pulse Rate (Hz)/Desired Cmd. (Hz))/(120/Motor
Poles)
Defines if the input wired to terminals 5 and 6 of the Encoder Terminal Block will be
used as a Pulse or Marker Input. Options 1 and 3 detect a loss of signal (when using
differential inputs) regardless of the Feedback Select (80) setting. When option 2 or 3
are used with Profile/Indexer Mode, the “homing” routine will position to the nearest
marker pulse off of the home limit switch.
422
Pulse ln Scale
Range:
2 to 20000 [1]
Default:
64
Access:
1
Path: Motor Control>Speed Feedback
See also:
FV
423
Encoder Z Chan
Range:
0 = Pulse Input
Default:
0 = Pulse Input
1 = Pulse Check
2 = Marker Input
3 = Marker Check
Access:
1
Path: Motor Control>Speed Feedback
See also:
FV