322 analog in 1 hi, 323 analog in 1 lo – Rockwell Automation Liqui-Flo DBT Reach Drive User Manual

Page 110

Advertising
background image

3-84

DBT Reach Drive User Manual

Analog In 1 Hi sets the highest input value to the analog input 1 scaling block.

Anlg ln Config (320) defines if the input value will be -/+10V or 0-20 mA.

Sets the lowest input value to the analog input 1 scaling block.

Anlg ln Config (320) defines if the input value will be -/+10V or 0-20 mA.

If set below 4 mA, Analog ln x Loss (324) should be “Disabled.”

322

Analog In 1 Hi

Range:

0.000 to 20.000 mA [0.001 mA]
-/+10.000 V [0.001 V]
0.0 to 10.000 V [0.001 V]

Default:

20.000 mA

Access:

0

Path: Inputs & Outputs>Analog Inputs

See also:

91, 92

Analog Input Scaling Example

Assume:

Speed Ref A Sel = Analog In 1

Minimum Freq = 0 Hz

Maximum Freq = 60 Hz

Analog In 1 Lo = 0.0 V

Analog In 1 Hi = 10.0 V

This is the default setting, where minimum input (0 V) represents Minimum Speed
and maximum input (10 V) represents Maximum Speed.

323

Analog In 1 Lo

Range:

0.000 to 20.000 mA [0.001 mA]
-/+10.000 V [0.001 V]
0.0 to 10.000 V [0.001 V]

Default:

4.000 mA

Access:

0

Path: Inputs & Outputs>Analog Inputs

See also:

91, 92

Advertising