72 break frequency, 79 speed units, 80 feedback select – Rockwell Automation Liqui-Flo DBT Reach Drive User Manual

Page 42

Advertising
background image

3-16

DBT Reach Drive User Manual

Sets the frequency the drive will output at Break Voltage (71).

Selects the units to be used for all speed related parameters. Options 0 and 1 indicate
status only. Options 2 and 3 will convert and/or configure the drive for that selection.

Convert Hz (2) = Converts all speed based parameters to Hz and changes the value
proportionately (i.e. 1800 RPM = 60 Hz).

Convert RPM (3) = Converts all speed based parameters to RPM and changes the
value proportionately.

Selects the source for motor speed feedback. Note that all selections are available
when using Process PI.

72

Break Frequency

Range:

0.0 to Maximum Freq [0.1 Hz]

Default:

Motor NP Freq x 0.25

Access:

2

Path: Motor Control>Volts per Hertz

See also:

53, 71

79

Speed Units

Range:

0 = Hz
1 = RPM
2 = Convert Hz
3 = Convert RPM

Default:

0 = Hz

Access:

0

Path: Speed Command>Spd Mode & Limits

See also:

80

Feedback Select

Range:

0 = Open Loop
1 = Slip Comp
2 = Reserved
3 = Encoder
4 = Reserved
5 = Simulator

Default:

0 = Open Loop

Access:

2

Path: Speed Command>Spd Mode & Limits

See also:

53, 152, 412