150 drive ol mode, 151 pwm frequency, 152 droop rpm @ fla – Rockwell Automation Liqui-Flo DBT Reach Drive User Manual

Page 65

Advertising
background image

Parameter Descriptions

3-39

Selects the drive’s response to increasing drive temperature and may reduce the
current limit value as well as the PWM frequency. If the drive is being used with a sine
wave filter, the filter is likely tuned to a specific carrier frequency. To ensure stable
operation, it is recommended that Drive OL Mode be set to 1 = Reduce CLim.

Sets the carrier frequency for the PWM output. Drive derating may occur at higher
carrier frequencies. For derating information, refer to Appendix A.

Important: If Motor Cntl Sel (53) is set to FVC Vector, the drive will run at 2kHz

carrier frequency when operating below 6 Hz.

Selects amount of droop that the speed reference is reduced when at full load torque.
Zero disables the droop function.

Important: Selecting “Slip Comp” with Feedback Select (80) in conjunction with

Droop RPM @ FLA may produce undesirable results.

150

Drive OL Mode

Range:

0 = Disabled
1 = Reduce CLim
2 = Reduce PWM
3 = Both-PWM 1st

Default:

3 = Both-PWM 1st

Access:

1

Path: Dynamic Control>Load Limits

See also:

219

151

PWM Frequency

Range:

2 - 10kHz [2/4/8/10 kHz]

Default:

4 kHz
2 kHz (Frames 4-6, 575 VAC)

Access:

0

Path: Dynamic Control>Load Limits

See also:

FV

152

Droop RPM @ FLA

Range:

0.0 to 200.0 RPM [0.1 RPM]

Default:

0.0 RPM

Access:

1

Path: Dynamic Control>Load Limits

See also:

FV