601 torqprove setup, 602 spd dev band, 603 spd band integrat – Rockwell Automation Liqui-Flo DBT Reach Drive User Manual
Page 143

Parameter Descriptions
3-117
Load Spd Lim = Enables drive to perform load calculation at base speed. Drive will
then limit operation above base speed depending on load.
NoEnclsBkSlp = A “1” disables the partial Brake Slip routine from the drive when
encoderless is selected.
Allows control of specific torque proving functions through a communication device.
Defines the allowable difference between the commanded frequency and encoder
feedback value. A fault will occur when the difference exceeds this value for a period
of time.
Sets the amount of time before a fault is issued when Spd Dev Band (602) is outside
its threshold.
601
TorqProve Setup
Range:
See figure 3.40
Default:
See figure 3.40
Access:
2
Path: Applications>Torque Proving
See also:
Figure 3.40 – TorqProve Setup
0
0
0
0
x
x
x
x
x
x
x
x
x
x
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1 =Enabled
0 =Disabled
x =Reserved
Bit #
Factory Default Bit Values
Fast Stop
Micr
o P
os
Decel Limit
End Stop
602
Spd Dev Band
Range:
0.1 to 15.0 Hz or 3.0 to 450.0 RPM [0.1 Hz or 0.1 RPM]
Default:
2.0 Hz or 60.0 RPM
Access:
2
Path: Applications>Torque Proving
See also:
603
603
Spd Band Integrat
Range:
1 to 200 mSec [1 mSec]
Default:
60 mSec
Access:
2
Path: Applications>Torque Proving
See also:
602