601 torqprove setup, 602 spd dev band, 603 spd band integrat – Rockwell Automation Liqui-Flo DBT Reach Drive User Manual

Page 143

Advertising
background image

Parameter Descriptions

3-117

Load Spd Lim = Enables drive to perform load calculation at base speed. Drive will
then limit operation above base speed depending on load.

NoEnclsBkSlp = A “1” disables the partial Brake Slip routine from the drive when
encoderless is selected.

Allows control of specific torque proving functions through a communication device.

Defines the allowable difference between the commanded frequency and encoder
feedback value. A fault will occur when the difference exceeds this value for a period
of time.

Sets the amount of time before a fault is issued when Spd Dev Band (602) is outside
its threshold.

601

TorqProve Setup

Range:

See figure 3.40

Default:

See figure 3.40

Access:

2

Path: Applications>Torque Proving

See also:

Figure 3.40 – TorqProve Setup

0

0

0

0

x

x

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Enabled
0 =Disabled
x =Reserved

Bit #

Factory Default Bit Values

Fast Stop

Micr

o P

os

Decel Limit

End Stop

602

Spd Dev Band

Range:

0.1 to 15.0 Hz or 3.0 to 450.0 RPM [0.1 Hz or 0.1 RPM]

Default:

2.0 Hz or 60.0 RPM

Access:

2

Path: Applications>Torque Proving

See also:

603

603

Spd Band Integrat

Range:

1 to 200 mSec [1 mSec]

Default:

60 mSec

Access:

2

Path: Applications>Torque Proving

See also:

602