130 pi prop gain, 131 pi lower limit, 132 pi upper limit – Rockwell Automation Liqui-Flo DBT Reach Drive User Manual

Page 60: 133 pi preload

Advertising
background image

3-34

DBT Reach Drive User Manual

Sets the value for the PI proportional component when the PI Hold bit of PI Control
(125) = Enabled (1).

PI Error x PI Prop Gain = PI Output

Sets the lower limit of the PI output. This value must be less than the value set in PI
Upper Limit (132).

Sets the upper limit of the PI output. This value must be greater than the value set in
PI Lower Limit (131).

130

PI Prop Gain

Range:

0.00 to 100.00 [0.01]

Default:

1.00

Access:

2

Path: Speed Command>Process PI

See also:

124-138

131

PI Lower Limit

Range:

-/+400.0 Hz or -/+ 800.0% [0.1 Hz or .01%]

Default:

-Maximum Freq or -100%

Access:

2

Path: Speed Command>Process PI

See also:

79, 124-138

132

PI Upper Limit

Range:

-/+400.0 Hz or -/+ 800.0% [0.1 Hz or 0.1%]

Default:

+Maximum Freq 0r 100%

Access:

2

Path: Speed Command>Process PI

See also:

79, 124-138

133

PI Preload

Range:

PI Lower Limit to PI Upper Limit [0.1 Hz or 0.1%]

Default:

0.0 Hz or 100%

Access:

2

Path: Speed Command>Process PI

See also: 79, 124-138

Advertising