Appendix D-8

DBT Reach Drive User Manual

PI Enable

The output of the PI loop can be turned on (enabled) or turned off (disabled). This
control allows the user to determine when the PI loop is providing part or all of the
commanded speed. The logic for enabling the PI loop is shown below.

The drive must be running for the PI loop to be enabled. The loop will be disabled
when the drive is ramping to a stop (unless “Stop Mode” is configured in [PI
Configuration]), jogging or the signal loss protection for the analog input(s) is sensing
a loss of signal.

If a digital input has been configured to “PI Enable,” two events are required to enable
the loop: the digital input must be closed AND bit 0 of the PI Control parameter must
be = 1.

Figure D.10 – PI Loop Logic

Drive

Running

Drive

Ramping

to Stop

Drive

Jogging

Bit 0 of

[PI Control] = 1

(enabled)

[PI Configuration]

Signal Loss

The Configured

Digital Input

is Closed

A Digital Input

is Configured

to PI Enable

"Enabled" Status

Digital Input

is Reflected

in [PI Status]

Bit 0 = 1

The PI Loop

is Enabled

Bit 0

Bit 6