3-50

DBT Reach Drive User Manual

Sets the time that the drive will remain in power loss mode before a fault is issued.

When set to a non-zero value, selects the change in level at which the Power Loss will
occur.

The drive can use the percentages referenced in Power Loss Mode (184) or a trigger
point can be set for the line loss detection as follows:

V

Trigger

= [DC Bus Memory] - [Power Loss Level]

A digital input (programmed to 29 = Pwr Loss Lvl) is used to toggle between fixed
percentages and the detection level.

Sets the percentage of motor nameplate torque at which a load loss alarm will occur.

185

Power Loss Timer

Range:

0.0 to 60.0 sec [0.1 sec]

Default:

0.5 sec

Access:

1

Path: Dynamic Control>Power Loss

See also:

184

186

Power Loss Level

Range:

0.0 to 999.9 [0.1 VDC]

Default:

Drive Rated Volts

Access:

1

Path: Dynamic Control>Power Loss

See also:

!

ATTENTION:

If the value for Power Loss Level (186) is greater than

18% of DC Bus Memory (13), the user must provide a minimum line
impedance to limit inrush current when the power line recovers. The
input impedance should be equal to or greater than the equivalent of a
5% transformer with a VA rating 5 times the drive input VA rating. Failure
to observe this precaution could result in damage to equipment.

187

Load Loss Level

Range:

0.0 to 800.0% [0.1%]

Default:

200.0%

Access:

2

Path: Dynamic Control>Power Loss

See also:

211, 259