3-126

DBT Reach Drive User Manual

Provides an internal fixed voltage command value that is available as a selection for
Adj Volt Select (651).

Sets the low limit for the voltage reference when Motor Cntrl Sel (53) is set to “Adj
Voltage.”

Displays the voltage value of the reference specified Adj Volt Select (651).

Sets the rate for the MOP.

654
655
656
657
658
659
660

Adj Volt Preset 1
Adj Volt Preset 2
Adj Volt Preset 3
Adj Volt Preset 4
Adj Volt Preset 5
Adj Volt Preset 6
Adj Volt Preset 7

Range:

0.0/Drive Rated Volts [0.1 VAC]

Default:

0.0 VAC

Access:

2

Path: Applications>Adjust Voltage

See also:

661

Min Adj Voltage

Range:

0.0/Drive Rated Volts [0.1 VAC]

Default:

0.0 VAC

Access:

2

Path: Applications>Adjust Voltage

See also:

662

Adj Volt Command

Range:

0.0/Drive Rated Volts [0.1 VAC]

Default:

Read Only

Access:

2

Path: Applications>Adjust Voltage

See also:

663

MOP Adj VoltRate

Range:

0.1 to 100.0 V/s [0.1 V/s]

Default:

Read Only

Access:

2

Path: Applications>Adjust Voltage

See also: