3-54

DBT Reach Drive User Manual

Resets all parameter values to defaults except Language (201), Param Access Lvl
(196), Voltage Class (202) and Torq Prove Cnfg (600).

Option 1 resets the drive to factory settings based on Voltage Class.

Options 2 and 3 resets the drive to factory settings and sets alternate voltage and
current ratings.

Important: For Frames 5 and 6, the internal fan voltage may have to be changed

when using Option 2 or 3.

Loads a previously saved set of parameter values from a selected user set location in
drive non-volatile memory to active drive memory.

This parameter is disabled while Dynamic User Set mode is active. Dyn UserSet Cnfg
(204), Dynamic Mode bit (0) = Enabled (1).

197

Reset to Defalts

Range:

0 = Ready
1 = Factory
2 = Low Voltage
3 = High Voltage

Default:

0 = Ready

Access:

0

Path: Utility>Drive Memory

See also: 41-47, 54, 55, 62, 63, 69-72, 82, 148, 158

198

Load Frm Usr Set

Range:

0 = Ready
1 = User Set 1
2 = User Set 2
3 = User Set 3

Default:

0 = Ready

Access:

1

Path: Utility>Drive Memory

See also:

199

!

ATTENTION: The Reach Drive can be configured to use multiple saved
parameter (user) sets. Caution must be utilized to ensure that each user
set is programmed for proper operation for the application. Recalling an
improperly programmed user set may cause rotation of the motor in an
undesired direction at unexpected speeds or may cause unpredictable
starting of the drive and motor. Failure to observe this precaution could
result in damage to equipment, severe bodily injury or loss of life.