Rockwell Automation Liqui-Flo DBT Reach Drive User Manual

Page 134

Advertising
background image

3-108

DBT Reach Drive User Manual

Selects the source of the external torque reference to the drive. How this reference is
used is dependent upon [Speed/Torque Mod].

Scales the upper value of the Torque Ref x Sel selection when the source is an analog
input.

Scales the lower value of the Torque Ref x Sel selection when the source is an analog
input.

427
431

Torque Ref A Sel
Torque Ref B Sel

Range:

0 = Torque Stpt1
1 = Analog ln 1
2 = Analog ln 2
3-17 = Reserved
18 = DPI Port 1
19 = DPI Port 2
20 = DPI Port 3
21 = DPI Port 4
22 = DPI Port 5
23 = Reserved
24 = Disabled
25 = Scale Block 1
26 = Scale Block 2
27 = Scale Block 3
28 = Scale Block 4
29 = Torque Stpt2

Default:

427: 0 = Torque Stpt1
431: 24 = Disabled

Access:

1

Path: Motor Control>Torq Attributes

See also: 53

FV

428
432

Torque Ref A Hi
Torque Ref B Hi

Range:

-/+ 800.0% [0.1%]

Default:

100.0%

Access:

1

Path: Motor Control>Torq Attributes

See also: 53

FV

429
433

Torque Ref A Lo
Torque Ref B Lo

Range:

-/+ 800.0% [0.1%]

Default:

0.0%

Access:

1

Path: Motor Control>Torq Attributes

See also: 53

FV