The input functions are:

1 = Enable: If the input is closed, the drive can run (start permissive). If the input is
open, the drive will not start.

If the drive is already running when this input is opened, the drive will coast and
indicate “not enabled” on the HIM (if present). This is not considered a fault condition,
and no fault will be generated.

If multiple enable inputs are configured, the drive will not run if any of them are open.

2 = Clear Faults: This function allows an external device to reset drive faults through
the terminal block if Logic Source Sel (89) is set to Terminal Blk or All Ports. An
open-to-closed transition on this input will reset the current fault (if any).

If this input is configured at the same time as Stop-Clear Faults, then only the Clear
Faults input can actually cause faults to be reset.

3 = Aux Fault: If the function loss input is open, a fault is generated. The function loss
input is active at all times regardless of the selected logic control source.

Important: The function loss input is not intended for a fast output power kill. The

drive will not fault until the software detects the change of state of this
input. If this input function is not configured, the fault will not occur.

Table 3.5 – Spd/Trq Sel # Inputs

Speed/Torque Select Inputs (33, 32, 31)

3

2

1

Reference Source

0

0

0

Zero Torque

0

0

1

Speed Regulator

0

1

0

Torque Regulator

0

1

1

Min Speed/Torque

1

0

0

Max Speed/Torque

1

0

1

Sum Speed/Torque

1

1

0

Absolute

1 1

1

Zero

Torque

Table 3.6 – Default Values for Parameters 361-366

Parameter No.

Default Value

361

4 = Stop-CF

362

5 = Start

363

3 = Function Loss

364

10 = Jog

365

18 = Auto/Manual

366

15 = Speed Sel 1