Appendix a, Ppendix, Technical specifications – Rockwell Automation Liqui-Flo DBT Reach Drive User Manual

Page 197

Advertising
background image

Technical Specifications

A-1

A

PPENDIX

A

Technical Specifications

Table A.1 – Drive Monitoring and Limits

All Drives

Heat Sink Thermistor

Monitored by microprocessor overtemp trip

Drive Overcurrent Trip
Software Current Limit
Hardware Current Limit

200% of rated current (typical)
220-300% of rated current (Depending on drive rating)

Line Transients

up to 6000 volts peak per IEEE C62.41-1991

Control Logic Noise
Immunity

Showering arc transients up to 1500V peak

Power Ride-Thru

15 milliseconds at full load

Logic Control Ride-Thru 0.5 seconds minimum, 2 seconds typical

Ground Fault Trip

Phase-to-ground on drive output

Short Circuit Trip

Phase-to-phase on drive output

Intermittent Overload

110% overload capability for up to 1 minute.
150% overload capability for up to 3 seconds.

Current Limit Capability Proactive Current Limit programmable from 20 to 160% of

rated output current. Independently programmable
proportional and integral gain.

Electronic Motor
Overload
Protection

Class 10 protection with speed sensitive response.
Investigated by U.L. to comply with N.E.C. Article 430. U.L.
File E59272, volume 12.

Table A.2 – Certifications

The drive is designed to meet the following specifications:
NFPA 70 - US National Electrical Code
NEMA ICS 3.1 - Safety standards for Construction and Guide for Selection,

Installation and Operation of Adjustable Speed Drive Systems.

IEC 146 - International Electrical Code.