276 logic mask, 277 start mask, 278 jog mask – Rockwell Automation Liqui-Flo DBT Reach Drive User Manual

Page 99

Advertising
background image

Parameter Descriptions

3-73

.

Determines which ports can control the drive when Write Mask Act (597), bit 15 is set
to “1.” If the bit for a port is set to “0,” the port will have no control functions except for
stop.

Controls which adapters can issue start commands.

Controls which adapters can issue jog commands.

276

Logic Mask

Range:

See figure 3.27

Default:

See figure 3.27

Access:

2

Path: Communication>Masks & Owners

See also: 288-297

Figure 3.27 – Logic Mask (276)

1

1

1

1

1

1

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Control Permitted
0 =Control Mask
x =Reserved

Bit #

Digital In

DPI P

or

t 1

DPI P

or

t 2

DPI P

or

t 3

DPI P

or

t 4

DPI P

or

t 5

Factory Default Bit Values

277

Start Mask

Range:

See figure 3.27

Default:

See figure 3.27

Access:

2

Path: Communication>Masks & Owners

See also: 288-297

278

Jog Mask

Range:

See figure 3.27

Default:

See figure 3.27

Access:

2

Path: Communication>Masks & Owners

See also: 288-297

Advertising