4 troubleshooting the drive using the lcd him, 1 accessing the fault queue – Rockwell Automation Liqui-Flo DBT Reach Drive User Manual

Page 196

Advertising
background image

4-16

DBT Reach Drive User Manual

4.4

Troubleshooting the Drive Using the LCD HIM

The LCD HIM provides immediate visual notification of alarm or fault conditions as
well as the following diagnostic information:

Entries in the fault queue

Fault parameters

Drive status parameters

Selected device version and status information

HIM version information

4.4.1 Accessing the Fault Queue

As described in section 4.2.1, the drive automatically retains a history of the last 16
faults that have occurred in the fault queue.

To access the fault queue, press

or select Faults>View Fault Queue from the

Diagnostics Menu off of the main screen.

Figure 4.1 – Accessing the Fault Queue

FAULT
ALARM

Diagnostics

Faults

SEL

PARAM

DIAG

STARTUP

Alarms

Drive Status
Device Select
Device Name

Diagnostics

SEL

PARAM

DIAG

STARTUP

Alarms

Drive Status
Device Select
Device Name

Faults

Faults

Clear Faults

SEL

ALARMS

FAULTS

View Fault Queue

Clear Flt Queue

View Fault Queue

F02:Decel Inhibit

F01:Faults Cleared

F03:Undervoltage
F04:Port 1 DPI Loss
F05:Function Loss

Fault Queue 1

FltCode:52

01

Faults Cleared

Accumulated Time

319:40:03.000

FltQ #