Parameter Descriptions

3-7

The drive rated output current.

The Main Control board software version.

Set to match the type of motor connected: Induction, Synchronous Reluctance, or
Synchronous Permanent Magnet.

Important: Selecting option 1 or 2 also requires selection of “Custom V/Hz,” option 2

in Motor Cntl Sel (53).

Set to the motor nameplate rated volts. The motor nameplate base voltage defines the
output voltage when operating at rated current, rated speed, and rated temperature.

Set to the motor nameplate rated full load amps. The motor nameplate FLA defines
the output amps when operating at rated voltage, rated speed, and rated temperature.
It is used in the motor thermal overload and in the calculation of slip.

29

Control SW Ver

Range:

0.000 to 65535.000 [0.001]

Default:

Read Only

Access:

0

Path: Monitor>Drive Data

See also:

196

40

Motor Type

Range:

0 = Induction
1 = Synchr Reluc
2 = Synchr PM

Default:

0 = Induction

Access:

2

Path: Motor Control>Motor Data

See also:

53, 157, 158, 159

41

Motor NP Volts

Range:

0.0 to Drive Rated Volts [0.1 VAC]

Default:

Based on Drive Rating

Access:

1

Path: Motor Control>Motor Data

See also:

42

Motor NP FLA

Range:

0.0 to Rated Amps x 2 [0.1 Amps]

Default:

Based on Drive Rating

Access:

1

Path: Motor Control>Motor Data

See also:

47, 48