89 logic source sel – Rockwell Automation Liqui-Flo DBT Reach Drive User Manual

Page 46

Advertising
background image

3-20

DBT Reach Drive User Manual

Speed Reg (1) = Drive operates as a speed regulator.

Torque Reg (2) = An external torque reference is used for the torque command.

Min Torq/Spd (3) = Selects the smallest algebraic value to regulate to when the
torque reference and torque generated from the speed regulator are compared.

Max Torq/Spd (4) = Selects the largest algebraic value to regulate to when the torque
reference and torque generated from the speed regulator are compared.

Sum Torq /Spd (5) = Selects the sum of the torque reference and the torque
generated from the speed regulator.

Absolute Min (6) = Selects the smallest absolute algebraic value to regulate to when
the torque reference and torque generated from the speed regulator are compared.

Pos/Spd Prof (7) = Drive operates as a speed or position regulator as determined by
the steps configured by the Profile Step parameters (720-877) and Setup parameters
(705-719).

Selects the only control source for these logic commands:

Start (Run)

Jog

Direction

Clear Faults

Stop (Any attached HIM Stop Key is always functional. A Network stop command is
effective only for Network or All Ports. A Terminal Block Stop command is effective
only for Terminal Blk or All Ports.

Selecting All Ports (7) enables control from any control source (or port).

89

Logic Source Sel

Range:

0 = Terminal Blk
1 = Local HIM
2 = DPI Port 2
3 = DPI Port 3
4 = Reserved
5 = Network
6 = Reserved
7 = All Ports

Default:

1 = Local HIM

Access:

0

Path: Speed Command>Control Src Sel

See also: