259 alarm config 1, 261 alarm clear – Rockwell Automation Liqui-Flo DBT Reach Drive User Manual

Page 96

Advertising
background image

3-70

DBT Reach Drive User Manual

Enables/disables alarm conditions that will initiate a drive alarm.

Resets all Alarm1 - 8 Code parameters (262 - 269) to zero.

A code that represents a drive alarm. The codes will appear in the order that the
alarms occur. The first code in is the first out. A time stamp is not available with
alarms.

259

Alarm Config 1

Range:

See figure 3.25

Default:

See figure 3.25

Access:

2

Path: Utility>Alarms

See also:

Figure 3.25 – Alarm Config 1 (259)

0

0

0

0

0

0

x

0

0

0

0

0

0

0

0

0

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Condition True
0 =Condition False
x =Reserved

Bit #

Prec

hr

g Actv

UnderV

olta

ge

Po

wer Loss

Str At PwrUp

Anlg in Loss

IntDBRes OH

Dr

v OL Lvl 1

Dr

v OL Lvl 2

Decel Inhibt

W

aking

Motor Therm

In PhaseLoss

Load Loss

Gr

ound W

arn

Brk Slipped

0

0

x

x

x

x

x

x

x

x

x

x

x

x

x

26

16

17

18

19

20

21

22

23

24

25

27

28

29

30

31

1 =Condition True
0 =Condition False
x =Reserved

Bit #

Pr

of SetHome

PTC HW

Reser

ved

x

261

Alarm Clear

Range:

0 = Ready
1 = Clr Alarm Que

Default:

0 = Ready

Access:

1

Path: Utility>Alarms

See also:

262 - 269

262
263
264
265
266
267
268
269

Alarm 1 Code
Alarm 2 Code
Alarm 3 Code
Alarm 4 Code
Alarm 5 Code
Alarm 6 Code
Alarm 7 Code
Alarm 8 Code

Range:

0 to 65535 [1]

Default:

Read Only

Access:

1

Path: Utility>Alarms

See also:

261