Parameter Descriptions

3-53

Enables/disables the feature that saves the present MOP (motor-operated
potentiometer) frequency reference at power down or at stop.

Sets the rate of change of the MOP reference in response to a digital input.

Displays the present parameter access level.

The value of this parameter is not affected by a “Reset Defalts” command.

194

Save MOP Ref

Range:

See figure 3.9

Default:

See figure 3.9

Access:

2

Path: Utility>MOP Config

See also:

Figure 3.9 – Save MOP Ref (194)

0

x

x

0

x

x

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Save
0 =Do Not Save
x =Reserved

Bit #

Factory Default Bit Values

At P

owr Do

wn

At Stop

Nibble 1

Nibble 2

Nibble 3

Nibble 4

195

MOP Rate

Range:

0.2 to Maximum Frequency [0.1 Hz/sec]
6.0 to Maximum Frequency [0.1 RPM/sec]

Default:

1.0 Hz/sec or 30.0 RPM/sec

Access:

2

Path: Utility>MOP Config

See also:

196

Param Access Lvl

Range:

0 = Basic
1 = Standard
2 = Advanced

Default:

0 = Basic

Access:

2

Path: Utility>Drive Memory

See also: