Parameter Descriptions

3-25

Scales the lower value of the TB Man Ref Sel selection when the source is an analog
input.

Displays the pulse input value as seen at terminals 5 and 6 of the Encoder Terminal
Block if Encoder Z Chan (423) is set to “Pulse Input.”

Sets the output frequency/speed when a jog command is issued. Units are selected
by Speed Units (79).

Provides an internal fixed speed command value. In bipolar mode, direction is
commanded by the sign of the reference.

98

TB Man Ref Lo

Range:

-/+Maximum Speed [0.1 Hz or 0.01 RPM]

Default:

0.0

Access:

1

Path: Speed Command>Speed References

See also:

79, 96

99

Pulse Input Ref

Range:

-/+ 400.0 Hz or -/+ 24000.0RPM [0.1 Hz or 0.1 RPM]

Default:

Read Only

Access:

0

Path: Speed Command>Speed References

See also:

100

Jog Speed 1

Range:

+/- Maximum Speed [0.1 Hz or 0.1 RPM]

Default:

10.0 Hz or 300.0 RPM

Access:

0

Path: Speed Command>Discrete Speeds

See also:

79

101
102
103
104
105
106
107

Preset Speed 1
Preset Speed 2
Preset Speed 3
Preset Speed 4
Preset Speed 5
Preset Speed 6
Preset Speed 7

Range:

-/+Maximum Speed [0.1 Hz or 1 RPM]

Default:

See table 3.1

Access:

See table 3.1

Path: Speed Command>Discrete Speeds

See also:

79, 90, 93