Installation/Wiring

2-9

17

Current In Jumper

1

- Analog

In 1

Placing a jumper across
terminals 17 and 18 (or 19
and 20) will configure that
analog input for current.
(Parameter 320 must be set
ON.)

18

19

Current In Jumper

1

Analog In 2

20

21

–10V Pot Reference

2k ohm minimum load.

22

+10V Pot Reference

23

HW PTC Input 1

See above

24

+24VDC

5

Drive supplied logic input

power.

5

25

Digital In Common

26

24V Common

(5)

Common for internal power
supply.

27

Digital In 1

Stop -
CF

115V AC, 50/60 Hz - Opto
isolated
Low State: less than 30V AC
High State: greater than 100V
AC
24V DC - Opto isolated
Low State: less than 5V DC
High State: greater than 20V
DC
11.2 mA DC

361-
366

28

Digital In 2

Start

29

Digital In 3

Auto/M
an.

30

Digital In 4

Speed
Sel 1

31

Digital In 5

Speed
Sel 2

32

Digital In 6/Hardware Enable Speed

Sel 3

1.

Important: 4-20mA operation requires a jumper at terminals 17 and 18 (or 19 and 20). Drive damage may

occur if jumper is not installed.

2.

These inputs/outputs are dependant on a number of parameters (see “Rel. Param.).

3.

Differential Isolation - External source must be maintained at less than 160V with respect to PE. Input

provides high common mode immunity.

4.

Contacts in unpowered state. Any relay programmed as Fault or Alarm will energize (pick up) when power

is applied to drive and deengergize (drop out) when a fault or alarm exists. Relays selected for other
functions will energize only when that condition exists and will deenergize when condition is removed.

5.

150mA maximum load. Not present on 115V versions.

Table 2.2 – I/O Terminal Designations