Installation/Wiring

2-19

Example:

Using a 100 Ohm Pt RTD (a=0.00385) to measure temperatures from 0 degrees
Celsius to 200 degrees Celsius, the maximum resistance occurs at 200 degrees
Celsius and is approximately 177 Ohm. The maximum voltage across the sensor is
151 mV. If the x40 gain is used, the output voltage at 200 degrees Celsius is 6.04
Volts.

Digital I/O

The digital outputs are isolated with solid state relays. The outputs are internally short
circuit protected. The digital input is optically isolated.

2.5.7.3 Microcontroller Software

A microcontroller monitors three DIP switches to determine the operational mode of
the RTD board. A single “Mode” switch determines whether the board uses an internal
timebase or the digital input as a clock to step through the eight analog input
channels. When using the internal timebase, the other two DIP switches select one of
four clock periods.

Figure 2.10 – Scaled Analog Output for RTD Board

Analog Multiplexer

SA (1 of 8)

SB (1 of 8)

A0
A1
A2

DA

DB

NTC/RTD

Sourcing

Analog

Out

0-10V

12V

0.01

F

10

10

MAX4194

Instrumentation Amp

Rail-to-Rail

Gain Adjustable

Gain Adjust

DIP Switch Settings, S1

(overall gain)

50K

F

F

100K

100K

F

F

100K

100K

4th Order Low Pass Filter

F

C

= 16Hz

Channel
Address

x10

Gain = 1 + 50K/Rg

100K

11.1K

MAX4194

x10

Rg

12V

5V

LMC6484

Quad Op Amp

Rail-to-Rail

x20

x30

x40

x50

x60

x70

x80

up

down

S1