4.1

About Alarms

Alarms indicate conditions that may affect drive operation or application performance.

Alarms are automatically cleared when the condition that caused the alarm is no
longer present.

There are two alarm types, as described in table 4.1.

The drive indicates alarm conditions in the following ways:

Alarm name and bell graphic on the LCD HIM. The alarm is displayed as long as the
condition exists. The drive automatically clears the alarm when the condition
causing it is removed.

Alarm status parameters. Two 16-bit parameters, Drive Alarm 1 (211) and Drive
Alarm 2 (212), indicate the status of type 1 and type 2 alarms, respectively. Refer to
chapter 10 for the parameter descriptions.

Table 4.1 – Types of Alarms

Type

Alarm Description

User-Configurable These alarms alert the operator of conditions that, if left

untreated, may lead to a fault condition. The drive
continues to operate during the alarm condition.

The alarms are enabled or disabled using Alarm Config 1
(259).

The status of these alarms is shown in Drive Alarm 1
(211).

Non-Configurable

These alarms alert the operator of conditions caused by
improper programming and prevent the drive from starting
until the problem is resolved.

These alarms are always enabled.

The status of these alarms is shown in Drive Alarm 2
(212).