Parameter Descriptions

3-29

Sets the response time of slip compensation.

Displays the present amount of adjustment being applied as slip compensation.

Important: Parameters in the Process PI Group are used to enable and tune the PI

Loop. In order to allow the PI Loop to control drive operation, set PI
Control (125) to Enabled, bit 0 = 1.

Selects specific features of the PI regulator.

Bit 0 - Excl Mode (Exclusive Mode)

Enabled = Selects speed regulation.

Disabled = Selects trim regulation.

122

Slip Comp Gain

Range:

1.0 to 100.0 [0.1]

Default:

40.0

Access:

2

Path: Speed Command>Slip Comp

See also:

80, 121, 122

123

Slip RPM Meter

Range:

-/+300.0 RPM [0.1 RPM]

Default:

Read Only

Access:

2

Path: Speed Command>Slip Comp

See also:

80, 121, 122

124

PI Configuration

Range:

See figure 3.5

Default:

See figure 3.5

Access:

2

Path: Speed Command>Process PI

See also:

124-138

Figure 3.5 – PI Configuration (124)

0

0

0

0

0

0

0

0

0

0

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Enabled
0 =Disabled
x =Reserved

Bit #

Factory Default Bit Values

Exc

l Mode

In

ver

t Err

or

Preload Mode

Ramp Ref

Zer

o Clamp

Feedbak Sqr

t

Stop Mode

Anti-W

ind Up

Tor

que T

rim

% of Ref

x