238 fault config 1, 240 fault clear, 241 fault clear mode – Rockwell Automation Liqui-Flo DBT Reach Drive User Manual
Page 94

3-68
DBT Reach Drive User Manual
Enables/disables annunciation of the faults shown in figure 11.24.
Resets a fault and clears the fault queue.
Enables/disables a fault reset (clear faults) attempt from any source. This does not
apply to fault codes, which are cleared indirectly via other actions.
238
Fault Config 1
Range:
See figure 11.24
Default:
See figure 11.24
Access:
2
Path: Utility>Faults
See also:
Figure 3.24 – Fault Config 1 (238)
1
x
1
0
0
0
1
0
0
0
x
0
0
0
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1 =Enabled
0 =Disabled
x =Reserved
Bit #
Factory Default Bit Values
Po
wer Loss
UnderV
olta
ge
Motor OverLd
Shear Pin
A
utRst T
ries
Decel Inhibt
Motor Therm
In PhaseLoss
Load Loss
ShearPNo Acc
Out PhaseLoss
PTC HW
Reser
ved
Reser
ved
240
Fault Clear
Range:
0 = Ready
1 = Clear Faults
2 = Clr Flt Que
Default:
0 = Ready
Access:
2
Path: Utility>Faults
See also:
241
Fault Clear Mode
Range:
0 = Disabled
1 = Enabled
Default:
1 = Enabled
Access:
2
Path: Utility>Faults
See also:
3
3.24
3.24