26 calculate current controller parameters, 4drive interface – Lenze 9400 User Manual

Page 72

Advertising
background image

4

Drive interface

4.2

Device commands

72

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

4.2.26

Calculate current controller parameters

This function extension is available from software version V5.0 onwards!

The device command

C00002

= "77: Calculate current controller parameters" is used to calculate

the gain and the reset time of the current controller for a third-party motor.
Precondition: The two motor parameters "stator resistance" (

C00084

) and "stator leakage

inductance" (

C00085

) either have been parameterised manually on the basis of the manufacturer

information before, or have been determined automatically via the device command "

Determine

motor parameters

".

• The calculation is carried out according to the following formulas:

• After the device command has been executed successfully (see status in

C00003

), the two

calculated values are set in

C00075

and

C00076

. They serve as starting values for a subsequent

optimisation of the current controller in the test mode.

• In the event of an error, codes

C00075

and

C00076

are not altered.

Tip!
Detailed information on the optimisation of the current controller in the test mode can be

found in the chapter "Motor interface" in the subchapter for the respective motor control:

• Servo control (SC)

Optimising the current controller

( 144)

• Sensorless vector control (SLVC)

Optimising the current controller

( 178)

• V/f control (VFCplus)

Optimising the current controller

( 193)

Note!

For a Lenze motor the calculation and the subsequent optimisation of the current

controller parameters is not required, as the correct current controller parameters are

accepted from »Engineer« motor catalogue.
The device command is no identification procedure for determining the current

controller parameters!

Gain

Stator leakage inductance

340 μs

-------------------------------------------------------------------

=

Reset time

Stator leakage inductance

Stator resistance

-------------------------------------------------------------------

=