Basler Electric BE1-851 User Manual

Page 10

Advertising
background image

Application Firmware

Version and Date

Change

Setting groups can be changed during the reclosing sequence by

monitoring the 79 shot counter.

Changed the default settings for programmable variable names.

Defaults are now all set to generic variable names with state names of

TRUE or FALSE.

Re-ordered the output of the

S command to match the order of settings

as listed in the instruction manual, Appendix C.

2.41.00, 06/99

Added Modbus full write functionality.

Changed version format from x.xx to x.xx.xx.

Added Transducer Network Lite Protocol (TNP Lite).

Improved trip circuit monitor to allow use with ac trip voltage.

2.37, 11/98

Increased the range of breaker duty

I or I

2

accumulation from 2.17e7

to 4.2e7.

2.36, 09/98

Added Distributed Network Protocol (DNP) 3.0 with limited read and

control functions.

2.31, 02/98

Increase the range of the programmable 51 curve,

A coefficient, from 0

- 100 to 0 - 600.

2.27, 01/98

Improved 62 timer performance.

Changed minimum breaker failure time from 100 ms to 50 ms.

Added functionality to enable or disable targets for each protective

function.

Added functionality to allow HMI Alarm Reset pushbutton to be used as

a logic variable (RSTKEY).

Improved fault recording functions as follows:

o Phase, neutral, and negative-sequence currents are recorded

one cycle after the TRIP trigger logic becomes TRUE.

o Added programmable alarm for Fault Record Time Out and

changed the error readout to show N/A for this condition with

BREAKER OPERATE TIME and FAULT CLEARING TIME.

o Change the RF-TRIP to show RF=TRIG instead of SERIAL for

EVENT TYPE and FAULT TRIGGER.

o Second oscillographic record triggering point was changed from

when the TRIP trigger logic became TRUE, to when both PU

and LOGIC trigger logic became FALSE.

o Second oscillographic record was changed to record without a

gap between the first and second records during specific

conditions.

2.15, 05/97

Initial release

Hardware

Version and Date

Change

Version 4, 05/03

Added real time clock chip, 8-hour capacitor ride-through for real time

clock, optional battery backup for real time clock and jumper-selectable

voltage rating for the contact sensing inputs.

viii

BE1-851 Introduction

9289900990 Rev R