The RS-485 connector is a three-position terminal block connector designed to interface to a standard

communication cable. A twisted-pair cable is recommended. Connector pin numbers, functions, names,

and signal directions are shown in Table 12-3. A cable connection diagram is provided in Figure 12-24.

Table 12-3. RS-485 Pin-outs (COM2)

Terminal

Function

Name

Direction

A

Send/Receive A

(SDA/RDA)

In/Out

B

Send/Receive B

(SDB/RDB)

In/Out

C

Signal Ground

(GND)

N/A

Figure 12-24. RS-485 DB-37 to BE1-851

IRIG Input and Connections

The IRIG input is fully isolated and supports IRIG Standard 200-98, Format B002. The demodulated (dc

level-shifted) input signal must be 3.5 volts or higher to be recognized as a high logic level. The maximum

acceptable input voltage range is +10 to –10 volts. Input burden is nonlinear and rated at approximately

4kΩ at 3.5Vdc and approximately 3kΩ at 20Vdc.
IRIG connections are located on a terminal block shared with the RS-485 and input power terminals.

Terminal designations and functions are shown in Table 12-4.

02-20-97

D2557-11

22

6

4

A
B

C

3 POSITION TB

DB-37 FEMALE

TO BE1-851

TO RS422/RS485

19

24

C

B

A

A
B

C

4000'

MAX

.

COM 2

BE1-851

BE1-851

COM 2

BE1-851

COM 2

R

t

t

R

R = OPTIONAL TERMINATING

t

RESISTOR (120 OHMS TYP.)

A3

A4
A5

A3

A4
A5

A3
A4
A5

12-22

BE1-851 Installation

9289900990 Rev R